Lead time | Usually in Stock |
Main Input Voltage | 230 V |
Other Input Voltage | 220 V 240 V |
Main Output Voltage | 230 V |
Other Output Voltage | 220 V 240 V |
rated power in W | 2700 W |
Rated power in VA | 3000 VA |
Input Connection Type | BS1363A British IEC 60320 C20 Schuko CEE 7 / EU1-16P |
output connection type | 8 IEC 60320 C13 2 IEC Jumpers 2 IEC 60320 C19 |
Cable length | 2.44 m |
Number of cables | 3 |
Battery type | Lead-acid battery |
Provided equipment | CD with software Country-specific detachable power cord Documentation CD Installation guide Removable support feet USB cable Warranty card |
Battery recharge time | 3 h |
Number of battery replacement quantity | 1 |
Additional information | Configurable for 220 : 230 or 240 nominal output voltage |
Battery voltage | 96 V |
Battery charger power | 168 W rated |
Battery power in VAH | 505 VAh runtime |
Battery life | 3…5 year(s) |
Battery option | SRT96BP 1 1515 VAh SRT96BP 2 2525 VAh SRT96BP 3 3535 VAh SRT96BP 4 4545 VAh SRT96BP 5 5555 VAh SRT96BP 6 6565 VAh SRT96BP 8 8585 VAh SRT96BP 10 10605 VAh |
Extended runtime | 1 |
product web sub-family | High density |
Number of power module free slots | 0 |
Number of power module filled slots | 0 |
Redundant | No |
Colour | Black |
Height | 43.2 cm |
Width | 8.5 cm |
Depth | 63.5 cm |
Product weight | 31.3 kg |
Mounting location | Front |
Mounting preference | Lower |
Mounting mode | Rack-mounted with kit |
Two post mountable | 0 |
USB compatible | Yes |
Mounting position | Vertical |
Network frequency | 40...70 Hz auto-sensing |
Input voltage limits | 100...275 V adjustable (half load) |
Maximum configurable power in W | 2700 W |
Harmonic distortion | Less than 2 % |
Output frequency | 50/60 Hz +/- 3 Hz sync to mains |
Crest factor | 3 : 1 |
UPS type | Double conversion online |
Wave type | Sine wave |
bypass type | Internal bypass (automatic and manual) |
Maximum configurable power in VA | 3000 VA |
Product certifications | CE EAC RCM VDE |
marking | CE Mark |
Standards | EN/IEC 62040-1:2019/A11:2021 EN/IEC 62040-2:2006/AC:2006 EN/IEC 62040-2:2018 |
Ambient air temperature for operation | 0…40 °C |
Relative humidity | 0…95 % non-condensing |
Operating altitude | 0...10000 ft |
Ambient air temperature for storage | -15…45 °C |
Storage Relative Humidity | 0…95 % non-condensing |
Storage altitude | 0.00…15240.00 m |
Acoustic level | 55 dBA |
Heat dissipation | 703 Btu/h |
IP degree of protection | IP20 |
Free slots | 1 |
Alarm | Audible and visible alarms : prioritized by severity |
Emergency power off | Yes |
Surge energy rate | 340 J |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 24.6 cm |
Package 1 Width | 87.1 cm |
Package 1 Length | 59.9 cm |
Package 1 Weight | 36.74 kg |
Warranty | 3 years repair or replace (excluding battery) and 2 years for battery |
High density, double-conversion on-line power protection with scalable runtime.